riffin ha inviato un aggiornamento 5 anni, 2 mesi fa
Transformer Oil Dissolved Gas Analysis and Moisture Monitor
Model: PASL-3000
Description
HAOMAI innovatively combined semiconductor laser technology and photo-acoustic spectroscopy together and applied it to smart grid field.
The Transformer Oil Dissolved Gas Analysis and Moisture Monitor PASL-3000 developed by HAOMAI is capable to measure Hydrogen(H2), Carbon Monoxide(CO), Carbon Dioxide(CO2), Methane(CH4), Acetylene(C2H2), Ethane(C2H6), Ethylene(C2H4), moisture(H2O) etc. 8 types dissolved gases in transformer oil, which wins good reputation from numerous customers by convenient operation, easy maintenance and high measuring accuracy.
Main Features
●Advanced technology. Semiconductor laser technology and photo-acoustic spectroscopy are innovatively used for measuring dissolved gas in transformer oil. PASL-3000 has strong anti-cross interference ability, fast measuring response, high measuring accuracy, good repeatability etc.
●All-components dissolved gas measurement and analysis. Adopt photo-acoustic spectroscopy to measure gas component contents of Hydrogen(H2), Carbon Monoxide(CO), Carbon Dioxide(CO2), Methane(CH4), Acetylene(C2H2), Ethane(C2H6), Ethylene(C2H4), moisture(H2O) etc. 8 types gases, also can be extended to measure component contents of Nitrogen(N2) and Oxygen(O2).
●No consumables and no maintenance. There is no need for personnel to operate the equipment. No carrier gas or recalibration is required during operation. The constant maintenance is not needed.
●Reliable degassing. The monitor has a built-in constant temperature vacuum degassing device, which can degassing efficiently and quickly, and no pollution to oil samples.
●Multi-tank measurement. One monitor can measure up to three transformer tanks, and the longest pipe between transformer valve and equipment is 30m. The measurement is performed separately through the oil channel switch.
●Easy installation. Installation can be completed without power failure to reduce the economic loss of customers.
●Remote terminal display. The monitor supports MODBUS and IEC61850 protocol, which can provide remote terminal display, including equipment operation status, real-time measurement data, data column analysis graph, trend graph, report and warning prompt.
●Multiple data communication, remote centralized management. Advanced remote centralized management software can summarize and monitor the running status and test data of multiple monitors, and provide perfect trend analysis and diagnosis results. It supports RS485, Ethernet, GPRS, Optical Fiber etc. communication modes.
Technical Data
Power Supply220V, 2KW
Fault Gas TypeMinimum measuring limitMaximum measuring limit
Humidity10∼95% RH non-condensingH22 ppm5,000 ppm
Temperatureenvironment temperature: -40℃∼55℃(-10℃∼55℃ when starting)CO220 ppm20,000 ppm
oil temperature:: 10℃∼100℃CO20 ppm10,000 ppm
EnclosureIP55CH40.5 ppm2,000 ppm
Dimension850(W)x800(D)x1700(H)mmC2H20.2 ppm2,000 ppm
Weight<350kgC2H40.5 ppm2,000 ppm
Measuring AccuracyMinimum measuring limit or ±30% (whichever is greater)C2H60.5 ppm2,000 ppm
H2O0∼100%(RS) or given in ppm
Semiconductor Laser Technology and Photo-acoustic Spectroscopy are innovatively used for Transformer Oil Dissolved Gas Analysis and Moisture Monitor PASL-3000.Transformer Online DGA factory
website:http://www.haomaitest.net/transformer-online-dga/